Automated Day Tanks Systems and Automated Generator Base Tank Systems
Closed Top Diked
The Closed Top Diked Generator Base Tank is a single wall constructed tank secured in a covered dike (or rupture basin), and the rails of the dike have been designed to support the weight of the generator set. The cover for the dike is vented at one end and is designed to keep rain and debris from entering the dike. Each gusseted bolt hole on the dike has been designed and tested to support up to 4000 lbs. If this tank is UL Listed, it will include an emergency vent connection on the inner tank only. This connection can be fitted with an optional back pressure relief valve set at 8 oz.
Heavy gauge steel construction
Primary Tank constructed of:
10 Gage steel top
12 Gage steel bottom, sides, ends, and baffles

Dike constructed of:
7 Gage steel channel sides
10 Gage steel bottom, and ends
2" NPT fill connection
1 1/4" NPT normal vent connection inner tank
1" NPT fuel return
1" x 1/2" NPT removable fuel supply dip tube 1" NPT Level Switch connection
3/8" NPT exterior drain
No fixed heights (recommended maximum 36")
Each tank designed to your specifications
Tank baffles to increase structural strength and to cool fuel
Inner tank pressure tested to 3 psi
Four sided complete base enclosure
Interior - rust proofing epoxy coated
Exterior - E&CA gray enamel or optional gloss black black
Home | Day Tanks | Generator Base Tanks | Meter Panels | Enclosures| Pump Sets | Literature | Local Reps | Site Map | Contact Us
©2000-20012 Engine & Compressor Accessories